CC-Link slave terminal EL6711-0010
Status LEDs
Fieldbus connection
Top view

EL6711-0010 | CC-Link slave terminal

As an EtherCAT slave, the EL6711-0010 CC-Link slave terminal enables data exchange between EtherCAT and CC-Link. The terminal is a slave, both on the EtherCAT and on the CC-Link side, so that an EtherCAT master can exchange data with a CC-Link master via this terminal. All CC-Link-specific settings such as node address, baud rate, data size and many more are parameterized via the EtherCAT master. There is no need for complex configurations on the CC-Link side; no further parameterization via the CC-Link master is required.

Technical data EL6711-0010
Technology CC-Link slave terminal
Fieldbus CC-Link slave version 1.1 or 2.0 (parameterizable)
Number of fieldbus channels 1
Data transfer rates 156 kbaud…10 Mbaud
Bus interface 1 x open style connector, 5-pin, included
Max. number of bytes fieldbus 16 words (version 1.1) or 128 words (version 2.0)
Bus device
Hardware diagnosis status LEDs
Distributed clocks
Current consumption power contacts
Special features status LEDs
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/see documentation
Approvals/markings CE
Product announcement